Page 440 - 2015 Master Catalog
P. 440

DR-60-24

60W/2.5A DIN-Rail 24VDC Industrial Power Supply

                            Features

                                        •	 -20°C to 60°C operating temprature range
                                        •	 Can be installed on DIN-rail TS-35 / 7.5 or 15
                                        •	 Protections: Short circuit / Over load / Over voltage / Over temperature
                                        •	 Isolation class II
                                        •	 UL60950-1, TUV EN60950-1 approved

Hardware Specifications                                                  Over Load Protection
                                                                          •	105 -160% rated output power
Power                                                                     •	Protection type : Constant current limiting, recovers

      Power Input                                                           automatically after fault condition is removed
       •	Voltage Range: 88 to 264VAC; 124 to 370VDC
       •	Frequency Range: 47 to 63Hz                               Environment
       •	Efficiency: 84% AC Current (Typ.): 1.2 / 115VAC; 0.8A /
                                                                         Operating Temperature
         230VAC                                                           •	-20°C to 60°C (-4°F to 140°F)
       •	Inrush Current (Typ.): Cold Start 18A / 115VAC; 36A /           Storage Temperature
                                                                          •	 -40°C to 85°C (-40°F to 185°F)
         230VAC                                                          Working Humidity
      Power Output                                                        •	20% to 90%RH non-condensing
       •	DC Voltage: 24V                                                 Storage Humidity
       •	Rated Current: 2.5A                                              •	10% to 95%RH
       •	Current Range: 0 to 2.5A                                  Regulatory Approvals
       •	Rated Power: 60W
       •	Ripple & Noise (max.): 150mVp-p                                 Safety
       •	Voltage Adj. Range: 21.6 to 26.4V                                •	UL60950-1, TUV EN60950-1 approved, design refer to
       •	Voltage Tolerance: + / - 1.0%
       •	Line Regulation: + / - 1.0% Load Regulation: + / - 1.0%            EN50178
       •	Setup, Rise Time: 100ms, 30ms / 230VAC; 200ms, 30ms /           EMC
                                                                          •	EN55011
         115VAC at full load                                              •	EN55022 (CISPR22) Class B
       •	Hold up Time: 100ms / 230V                                       •	EN61000-3-2, -3
                                                                          •	Withstand Voltage:
Mechanical
                                                                             ◦◦ I/P-O/P: 3KVAC
      Casing                                                              •	Isolation Resistance:
       •	Plastic Case
      Dimensions                                                             ◦◦ I/P-O/P: 100M Ohms / 500VDC
       •	78mm (W) x 56mm (D) x 93mm (H)                                  EMS Immunity
                                                                          •	EN61000-4-2,3,4,5,6,8,11
         (3.17" (W) x 2.2" (D) x 3.66" (H))                               •	ENV50204
      Weight                                                              •	EN55024
       •	 0.3Kg                                                           •	N61000-6-2
      Installation                                                        •	EN61204-3, EN50082-2, Heavy industry level, criteria A
       •	DIN-Rail                                                        Environmental Test Compliance
    Protection                                                            •	Vibration 10 to 500Hz, 2G 10min. / 1 cycle, period for 60
      Over Voltage Protection
       •	27.6 - 32.4V                                                       min. each along X, Y, Z axes
       •	Protection type : Shut down o/p voltage , re-power on to

         recover

DR-60-24                                                           28 www.EtherWAN.com

                                                                                                                                                        rev. A1.1
   435   436   437   438   439   440   441   442   443   444   445